Researching Parameters Selection, Testing Circuit Configuration in Lightning Impulse Test for 500kV Single Phase Power Transformer Produced in Vietnam

Authors: Nguyen Huu Kien*

Abstract

This article presents the result of researching in parameters selection in testing circuit configuration for the lightning impulse (LI) 1.2 /50 s power transformers which was produced in Viet Nam. This test was performed at The National Key Laboratory for High Voltage Techniques (HVLAB) - Institute of Energy, the unique laboratory in Vietnam where this test can be perform. In order to research the lightning impluse parameters and determine the endurance of high-voltage and ultra-high electrical equipment insulation in general and particularly for 500kV power transformer, it is necessary to set a simulation voltage of standard lightning impulse at 1.2 /50 s. These results will allow evaluating the quality of the insulation system in 500kV power transformer, the withstand ability of atmospheric overvoltage or operation overvoltage according to IEC60076-3,-4: 2000, TCVN6306- 3: 2006; IEC60060-1: 1989, in order to obtain safety power transformer operation in gridline.

Keyword

Lightning Impulse (LI), Switching Impulse (SI), International Electrotechnical Commission (IEC).
Pages : 19-24

Related Articles:

Authors : Lê Minh Hoàng*, Nguyễn Trung Kiên, Stephane Ploix
Authors : Nguyễn Thị Kim Thoa*, Nguyễn Minh, Nguyễn Hải Đăng, Phạm Hồng Thịnh, Phạm Ngọc Nam
Authors : Nguyen Van Cuong, Le Dinh Tuyen, Dao Vu Tuan, Tran Thanh Hai, Pham Ngoc Nam*
Authors : Cung Thành Long*, Bùi Đăng Thảnh*, Đào Đức Thịnh, Nguyễn Văn Tùng