Selection of Sheath Voltage Limiter for Mixed Overhead-Underground Cable in 220 kV Transmission Lines

Authors: Pham Thanh Chung*, Pham Hong Thinh, Tran Van Top
https://doi.org/10.51316/jst.161.etsd.2022.32.4.10

Abstract

This paper presents the most common methods of sheath bonding of transmission cables and the calculation of parameters, including rated voltage and energy absorption, of sheath voltage limiters for a mixed overhead-underground 220 kV transmission lines. The dependence of sheath voltage limiters parameters on the sheath types, system parameters such as the short-circuit capacity, the cable length, lightning current amplitudes, grounding resistance and cable installation are calculated in details. In this research, several methods in selecting sheath bonding types as well as sheath voltage limiters for a given set of conditions in mixed overhead-cable 220 kV transmission lines are proposed. The cross bonding permits to choose SVLs with the lowest rating voltage. However, the grounding resistance value of the tower at the junction between overhead lines and cables must be maintained at or below 3 Ω. The surrounding environment of cables changes, the required parameters of SVL to be selected must be recalculated to take the cable installation into account.

Keyword

Sheath Voltage Limiter, sheath voltage, sheath interruption voltage, energy absorption, lightning overvoltage, mixed line, EMTP-ATP
Pages : 69-78

Related Articles:

Authors : Vu Minh Hieu, Ho Huu Chan, Le Van Cong, Park Chan Woo, Tran Dang Quoc*
Authors : Ta Hong Duc, Cao Hong Ha*, Nguyen Trung Dung, Phan Ngoc Quang, Pham Duc Anh, Do Nguyen Ha Thu, Nguyen Van Anh
Authors : Nguyen Thi Thanh Lan, Nguyen Thi Hai Yen, Luu Thi Lan Anh, Chu Manh Hoang*